Mount the i/o adapter, Mount the point i/o adapter on a din rail – Rockwell Automation 1738-AENTR, Series A 1734 POINT I/O and 1738 ArmorPOINT I/O 2 Port Ethernet/IP Adapter User Manual User Manual

Page 19

Advertising
background image

Rockwell Automation Publication 1734-UM014B-EN-P - June 2013

11

Install Your Adapter Chapter 2

Mount the I/O Adapter

Use the following procedures to mount the I/O adapters on a new system before
you install any I/O modules.

Mount a 1734-FPD module in the slot next to the I/O adapter when applying
field power. You can also use the 24V DC to power the adapter to supply field
power, where no FPD is necessary. Refer to Point I/O Field Potential
Distribution Module Installation Instructions, publication

1734-IN059

for more

information.

Mount the POINT I/O Adapter on a DIN Rail

Position the I/O adapters vertically above the DIN rail.

1. Make sure the DIN rail locking screw (orange) is in horizontal position.
2. Position the adapter vertically above an IEC standard (35 x 7.5 x 1 mm)

top-hat DIN rail at a slight angle (DIN rail: Allen-Bradley part number

199-DR1; 46277-3).

3. Press down firmly to install the adapter on the DIN rail, noting that the

locking mechanism locks the adapter to the DIN rail.

4. Set the network address thumbwheel switches to the desired value.Set the

network address thumbwheel switches to the desired value. See

Set the

Network Address

in chapter

3

for more details on setting the IP address.

1734-AENTR

Module
Status

Network
Activity

Network
Status

Point Bus
Status

System
Power

Field
Power

POINT I O

75.30

(2.96)

74.00

(2.91)

132.72

(5.23)

52.23

(2.06)

35.55

(1.40)

A

B

45174

A = DIN rail
B = Secure DIN rail approximately every 200 mm (7.8 in.)