Setting the controlnet network address, Sw 1 sw 2 – Rockwell Automation 1788-CN2FF ControlNet to Foundation Fieldbus H1 Linking Device Installation Instructions User Manual
Page 14

14 ControlNet-to-Foundation Fieldbus H1 Linking Device
Publication 1788-IN051D-EN-P - February 2004
Setting the ControlNet Network Address
Valid ControlNet network addresses are 1-99. Network address zero is reserved. Switch 1
controls the most significant decimal digit (the tens). Switch 2 controls the least significant
decimal digit (the ones). Figure 6 shows the location of the network address switches and an
example of switch settings for a network address of 15.
Figure 6 ControlNet Network Address Switches Set to 15
Follow these steps to set the ControlNet network address for the 1788-CN2FF.
1. Choose and set a network address.
2. Write the network address setting in the space provided on the CN2FF label.
3. Apply (or cycle) power to the CN2FF to enable the new network address.
4. Make the same address changes in your NI-FBUS configuration software.
1
2 3 4
5
6
78
9
0
1
2 3 4
5
6
78
9
0
1
2 3 4
5
6
78
9
0
1
2 3 4
5
6
78
9
0
43164
Switch Cover
(Removed)
SW 1
SW 2