Device vs. connection clarifications – Rockwell Automation 1788-CN2FF ControlNet to Foundation Fieldbus H1 Linking Device Installation Instructions User Manual
Page 18
 
18 ControlNet-to-Foundation Fieldbus H1 Linking Device
Publication 1788-IN051D-EN-P - February 2004
Device vs. Connection Clarifications
This section describes the functional relationship and differences between 1788-CN2FF 
Connections and Foundation Fieldbus
ΤΜ
Devices. A connection does not always equal a
device.
• A connection is considered any link (wire connection) to:
• CNAI, ControlNet ANALOG INPUT
• CNAO, ControlNet ANALOG OUTPUT
• CNDI, ControlNet DIGITAL INPUT
• CNDO, ControlNet DIGITAL OUTPUT
• A device is considered a specific Foundation Fieldbus device such as a
transmitter.
For each different network configuration, you must account for all connections and devices 
toward the maximum recommendations.
ATTENTION
The maximum number of “connections” is 30 per CN2FF. The 
recommended number of “devices” is 8 per H1 port on the 
CN2FF. If you exceed the maximum number of connections or 
the recommended number of devices, system performance could 
be compromised.