ControlNet-to-Foundation Fieldbus H1 Linking Device 23

Publication 1788-IN051D-EN-P - February 2004

Allen-Bradley and ProcessLogix are trademarks of Rockwell Automation.

RSLinx, RSLinx OEM, RSNetWorx are trademarks of Rockwell Software.

Foundation Fieldbus is a trademark of the Fieldbus Foundation.

Windows NT and 2000 are trademarks of the Microsoft Corporation.

Indicators

• Module Status

• ControlNet Status, 1 each connection

Connectors

• ControlNet - BNC connectors, provides redundancy

• two 10-position rotary switches

• Network Access Port - RJ45 (non-isolated)

• Fieldbus - 9-pin sub-D connectors

• Power Input Terminals:

-Torque 5-7 in-lb.
-Not to be used with combination of solid and stranded 16 GA wire

Conductors

Wire Size

Category

#22 AWG (0.355 SQmm) Copper Stranded wire to #14 AWG (2.08 SQmm)
Copper Stranded wire

60

°

C minimum

2

(1)

(2)

Certifications
(when product is marked)

c-UL-us

UL Listed Industrial Control Equipment, certified for US and
Canada

FCC

North American EMI Verification

Part 15-Class A-ICES003

C-Tick

(3)

Australian EMC Compliance

AS/NZS CISPR 11; Industrial Emissions

CE

(3)

European Union 89/336/EEC EMC Directive, compliant with:

EN 61000-6-4; Industrial Emissions
EN 50082-2;

Industrial Immunity

EN 61326;

Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

(1)

Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, “Industrial
Automation Wiring and Grounding Guidelines”.

(2)

Appropriate shielded cable is required for Electromagnetic compatibility (EMC) standards.

(3)

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Type