I/o memory mapping, I1:x.0/0, Input data file – Rockwell Automation 1762-IQ16 DC Input Module User Manual

Page 14: 1762 expansion i/o addressing

Advertising
background image

14 MicroLogix 1762-IQ16 DC Input Module

Publication 1762-IN010C-EN-P - June 2013

I/O Memory Mapping

Input Data File

For each input module, the input data file contains the current state of the field input points. Bit
positions 0…15 correspond to input terminals 0…15.

r = read only

1762 Expansion I/O Addressing

The addressing scheme for 1762 Expansion I/O is shown below.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

I1:x.0/0

Slot number

(1)

Data file

File Type
Input (I)

Slot delimiter

Word delimiter

Bit delimiter

Bit (0...15)

Word (always 0 for this module)

(1)

I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with slot 1.