Rockwell Automation 1762-IQ16 DC Input Module User Manual

Page 16

Advertising
background image

16 MicroLogix 1762-IQ16 DC Input Module

Publication 1762-IN010C-EN-P - June 2013

Vendor I.D. Code

1

Product type code

7

Product code

97

(1)

Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device.
Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field
device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field
devices connected to the positive side (+V) of the field supply are sourcing field devices.

Environmental

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20... 65 °C (-4...149 °F) See

Derating Charts on page 17

.

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10... 500 Hz

Altitude, operating, max

2000 m (6562 ft)

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Panel mount - 50 g
DIN mount - 40 g

Emissions

CISPR 11
Group 1, Class A

ESD immunity

IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges
4 kV indirect

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2700 MHz

Input

Attribute

Value

Advertising