Because of the many analog devices available and the wide variety
of possible applications, you must configure the module to conform
to the analog device and specific application that you have chosen.
Use the configuration information below to configure your module
to your specifications.

Dec. Bits

15 14 13 12 11 10 09

08

07 06 05 04 03 02 01 00

Description

Octal Bits

17 16 15 14 13 12 11

10

07 06 05 04 03 02 01 00

Description

Word 1

8

7

6

5

4

3

2

1

Range Selection Ć Channels 1 - 8

2

16

15

14

13

12

11

10

9

Range Selection Ć Channels 9 - 16

Input range selections allow the

Bit 01

Bit 00

Voltage or Current Input

Input range selections allow the

user to configure the inputs for any of

7 i

t lt

t

T

0

0

1 to 5V dc, 4 to 20mA (default)

user to configure the inputs for any of

7 input voltage or current ranges. Two

bits are required for each channel.

0

1

0 to 5V dc, 0 to 20mA

bits are required for each channel.

Bits 00 and 01 for channel 1, bits 02

and 03 for channel 2, etc.

1

0

Ć5 to +5V dc, Ć20 to +20mA

and 03 for channel 2, etc.

1

1

Ć10 to +10V dc, 0 to 10V dc

3

Real Time Sampling

Data

Format

Input

Type

Digital Filter

Real time sampling, data format, input

type and digital filter

Digital filter reduces effect of noise on input. (Default is no

filter.)

Input type, set bit for differential mode on all channels.

Reset (0) = singleĆended inputs (default)

Set (1)

= differential inputs

Real time sampling - Default is no RTS.

Data format - set to match

your processor.

BCD (default)

Reserved
Two's complement binary
Signed magnitude binary

Bit 10

(12)

Bit 09

(11)

0 0
0 1
1 0
1 1

4

Minimum sign bits, when set, designate negative minimum scaling values for the

corresponding input channels. Bit 00 corresponds to channel 1, bit 01 corresponds to

channel 2, etc.

Sign Bits, minimum scaling values

5

Maximum sign bits, when set, designate maximum scaling values that are negative.

Maximum scaling value must be greater than minimum on any particular channel. Bit 00

corresponds to channel 1, bit 01 corresponds to channel 2, etc.

Sign Bits, maximum scaling values

6, 8, 10, 12, 14, 16,

18, 20, 22, 24, 26,

28, 30, 32, 34, 36

Minimum scaling values for each channel. Enter in BCD format.

Channel 1 Ć minimum scaling

7, 9, 11, 13, 15, 17,

19, 21, 23, 25, 27,

29, 31, 33, 35, 37

Maximum scaling values for each channel. Enter in BCD format.

Channel 1 Ć maximum scaling

38

Offset calibration - Each bit represents a channel (bit 00 to channel 1, bit 01 to channel

2, etc.). When the bit is set, and a BTW has been sent, the module will read the channels

and adjust the offset to analog ground potential. In differential mode, bits 08 thru 15 (10

thru 17 in octal) are ignored. In current mode, apply 0mA.

Offset Calibration

39

Gain calibration - Each bit represents a channel (bit 00 to channel 1, bit 01 to channel 2,

etc). When the bit is set, and a BTW has been sent, the module will read the channels and

adjust the gain correction values. If used on +, 0 to 5, or 1 to 5V ranges, a value of 5V is

expected. If used on +10V range, 10V is expected. In differential mode, bits 08 thru 15 (10

thru 17 in octal) are ignored. In current mode, apply 20mA.

Gain Calibration

For detailed configuration

information, see chapter 2 of

your Analog Input User Manual

(publication 1771Ć6.5.115).

Configure the Module