Analog Input Module

12

Publication 1771Ć5.45 - July 1997

Default Configuration

If a write block of five words with all zeroes is sent to the module,
default selections will be:

1 to 5V dc or 4 to 20mA (dependent on configuration jumper
setting)

BCD data format

no real time sampling (RTS)

no filtering

no scaling

single-ended inputs

The front panel of the analog input module contains a green RUN
indicator and a red FAULT indicator. At power-up, the module
momentarily turns on the red indicator as a lamp test, then checks
for:

correct RAM operation

firmware errors

If there is no fault, the red indicator turns off.

RUN

FLT

10528ĆI

ANALOG

IN

(12 BIT)

Green RUN indicator

Red FAULT indicator

The green indicator comes on when the module is powered. It will
flash until the module is programmed. If a fault is found initially or
occurs later, the red fault indicator lights. The module also reports
status and specific faults (if they occur) in every transfer of data
(BTR) to the PC processor. Monitor the green and red indicators and
status bits in word 1 of the BTR file when troubleshooting your
module.

Interpret Status Indicators