Connect wiring to the field wiring arm – Rockwell Automation 1771-IFE/C INSTL.INSTRUCTIONS ANALOG INPU User Manual

Page 6

Advertising
background image

Analog Input Module

6

Publication 1771Ć5.45 - July 1997

Connect your I/O devices to the cat. no. 1771-WG wiring arm
shipped with the module.

!

ATTENTION: Remove power from the 1771 I/O
chassis backplane and field wiring arm before
removing or installing an I/O module.

Failure to remove power from the backplane or
wiring arm could cause module damage, degradation
of performance, or injury.

Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.

Input connections for the 1771-IFE module with:

single-ended inputs are shown on page

7

differential inputs are shown on page 8

Minimizing Ground Loops

To minimize ground-loop currents on input circuits:

use single-ended mode whenever possible

use 2-wire transmitters with a common power supply

separate 2-wire and 4-wire transmitters between different
modules

tie 4-wire transmitter and/or separate power supply grounds
together

Important: We do not recommend mixing 2-wire and 4-wire

transmitter inputs on the same module. Power supply
placement can make it impossible to eliminate ground
loops.

Cable Lengths

Recommended maximum cable length for voltage-mode input
devices is 50 feet. This recommendation is based on considerations
of signal degradation and electrical noise immunity in typical
industrial environments. Cable length for current-mode input
devices need not be as restrictive because analog signals from these
devices are less sensitive to electrical noise interference.

Connect Wiring to the

Field Wiring Arm