Getting Started in Report Generation
Chapter 5
5Ć6
The channel address is the extended address of the 1775-S4B scanner that
executes the procedure. This address has the following format (figure 5.2):
E2.7.t
where:
E2 = the module status area of PLC-3 memory
7 = the 1775-S4B scanner section of the module status area
t = the thumbwheel number on the 1775-S4B scanner
Figure 5.2
MSG Instruction Extended Addressing Format
Module status
area of PLCĆ3
memory
1775ĆS4B scanner
section of module
status area
1775ĆS4B scanner
thumbwheel
number
The message type must always be one, and the message itself should be a
report generation procedure name.
An example program using the message send instruction to execute a
report generation procedure appears in figure 5.3.
Figure 5.3
Example Rung Which Executes a Report Generation Procedure
I0012
12
MESSAGE TYPE
1
CTL=FB005:0000= 0
CHANNEL E2.7.1
@TIME
MSG
STAT
(EN)
12
STAT
(DN)
15
STAT
(ER)