Specifications – Rockwell Automation 1771-IR INSTL.INSTR RTD INPUT MODULE User Manual

Page 11

Advertising
background image

RTD Input Module

11

Publication 1771-5.50 – October 1996

Description

Value

Number of Inputs

6 RTD input channels

Module Location

1771 I/O Chassis

Sensor Type

100 ohm platinum (alpha = 0.00385) or 10 ohm copper
(alpha = 0.00386)
Other types may be used with report in ohms only

Units of measure

Temperature in

o

C

Temperature in

o

F

RTD resistance in ohms (10milliohms or 30milliohms
resolution)

Temperature Range

Platinum: –200 to +870

o

C (–328 to 1598

o

F)

Copper: –200 to +260

o

C (–328 to +500

o

F)

Resistance Range

1.00 to 600.00 ohms

Resolution

Platinum: 0.1

o

C (0.1

o

F)

Copper: 0.3

o

C (0.5

o

F)

Sensor Excitation

1mA constant current source supplied by module

Common Mode Rejection

120db @ 60Hz up to 1000V peak

Common Mode Impedance

Greater than 10 megohms

Normal Mode Rejection

60db @ 60Hz

Input Overvoltage Protection

120V rms continuous

Open RTD Response Time

Open excitation (terminal A) to overrange: <0.5sec
Open common (terminal C) to underrange: <0.5sec
Open sense (terminal B): drift high

Scan Time

50ms for 6 channels

Isolation Voltage

This isolation meets or exceeds the requirements of UL
Standard 508, and CSA Standard C22.2 No. 142.

Backplane Current

950mA at 5V

Power Dissipation

4.75W maximum

Thermal Dissipation

16.2 BTU/hr

Environmental Conditions

Operating Temperature:
Rate of Change:

Storage Temperature:
Relative Humidity:

Operating
Storage

0 to 60

o

C (32 to 140

o

F)

Ambient changes greater than 1.0

o

C/minute may temporarily

degrade performance during periods of change.
–40 to 85

o

C (–40 to 185

o

F)

5 to 95% noncondensing
5 to 95% noncondensing

Keying

Between 10 and 12
Between 28 and 30

Field Wiring Arm

Cat. No. 1771-WF

Wiring Arm Screw Torque

7-9 inch-pounds

Specifications continued on next page