Connect wiring to the field wiring arm – Rockwell Automation 1771-IR INSTL.INSTR RTD INPUT MODULE User Manual

Page 5

Advertising
background image

Connection Diagram for the RTD Input Module (1771-IR/C)

Field Wiring Arm

Cat. No. 1771-WF

18

17

16

1

15
14
13

12

11
10

9
8

7

6
5
4
3

2

11846-I

RTD

Ground

Chassis

(Channel 1 shown)

RTD Input Module

5

Publication 1771-5.50 – October 1996

Connect your I/O devices to the field wiring arm (cat. no. 1771-WF)
shipped with the module.

!

ATTENTION: Remove power from the 1771 I/O
chassis backplane and field wiring arm before
removing or installing an I/O module.

•

Failure to remove power from the backplane or
wiring arm could cause module damage, degradation
of performance, or injury.

•

Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.

Channel

Terminal

Identification

1

18

C

17

B

16

A

2

15

C

14

B

13

A

3

12

C

11

B

10

A

4

9

C

8

B

7

A

5

6

C

5

B

4

A

6

3

C

2

B

1

A

Connect Wiring to the
Field Wiring Arm

Advertising