Connect wiring to the field wiring arm – Rockwell Automation 1771-IR INSTL.INSTR RTD INPUT MODULE User Manual

Page 5

Advertising
background image

Connection Diagram for the RTD Input Module (1771-IR/C)

Field Wiring Arm

Cat. No. 1771-WF

18

17

16

1

15
14
13

12

11
10

9
8

7

6
5
4
3

2

11846-I

RTD

Ground

Chassis

(Channel 1 shown)

RTD Input Module

5

Publication 1771-5.50 – October 1996

Connect your I/O devices to the field wiring arm (cat. no. 1771-WF)
shipped with the module.

!

ATTENTION: Remove power from the 1771 I/O
chassis backplane and field wiring arm before
removing or installing an I/O module.

Failure to remove power from the backplane or
wiring arm could cause module damage, degradation
of performance, or injury.

Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.

Channel

Terminal

Identification

1

18

C

17

B

16

A

2

15

C

14

B

13

A

3

12

C

11

B

10

A

4

9

C

8

B

7

A

5

6

C

5

B

4

A

6

3

C

2

B

1

A

Connect Wiring to the
Field Wiring Arm

Advertising