Configure the module – Rockwell Automation 1771-IR INSTL.INSTR RTD INPUT MODULE User Manual

Page 7

Advertising
background image

RTD Input Module

7

Publication 1771-5.50 – October 1996

Use the configuration information below to configure your module
to your specifications.

Dec. Bits

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

De

o

Octal Bits

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Description

Word 1

Real Time Sampling -

default = no RTS

Data

Format

RTD

Type

Units of

Measure

Single channel in ohms

Real time sampling, data format, RTD
type units of measure, and single
channel in ohms

3.1s

In temperature mode:
0 = Entire module is platinum
1 = Entire module is 10 ohm copper.
Enter exact value in word 2.
In ohms mode:
0 = 30mohm/count resolution
1 = 10mohm/count resolution

If any of these bits are set, the corresponding input
channel will be reported in ohms. If RTDs other than 10
ohm copper or 100 ohm platinum are used you must
report those channels in ohms, not degrees. Data format
on a channel displayed in ohms will default to binary.

Determines what units of measure
the module reports.

Units of measure Bit 07 Bit 06

Degrees C

Degrees F

Ohms

Not used

0

0

0

1

1

0

1

1

Set to match your
processor.

BCD (default)

Reserved

Two’s complement binary

Signed magnitude binary

Bit 10 Bit 09

0

0

1

1

0

1

0

1

0.5s

0.4s

0.3s

0.2s

0.1s

1.0s

0.6s

0.7s
0.8s
0.9s

0

0

0

0
0

0

0

0

0

0

0

1

1
1

0

1

1

1
0

0

0

0

0

1

1
0

0
1

1

1

0

1

0

1

0

0

0

0

0

0

0

0

1

1

1

1

0

1

1

1

0

0

0

0

1

1

0

0

1

0

1

1

1

0

0

0

0

1

1.5s

2.0s

2.5s

3.0s

0

0

0

1

1

0

1

1

1

1

1

1

No RTS (50ms)

Important: Use decimally addressed bit

locations for PLC-5 processors.

2

If bit 10 is set in word 1, and temperature readings are desired, word 2 must also be used. Enter
the exact resistance of 10 ohm RTD at 25

o

C in BCD. Range is 9.00 to 11.00 ohms. Values less

than 9.00 ohms or greater than 11.00 ohms will default to 10.00 ohms. Non–BCD values will also
default to 10.00 ohms.

10 ohm resistance @ 25

_C

3, 4, 5, 6, 7, 8

Individual channel bias - entered in BCD. This value is subtracted from the channel data in the
BTR. The bias value is always a positive number. Bias value range is 0<bias<9999.

Channel 1-6 bias

9, 10, 11, 12, 13,

14, 15

Channel 1-6 calibration

Individual channel calibration

15

Not used

Channel failed calibration

FC

EE

Not used

S

G

O

auto-calibration request word

Offset calibration complete

Gain calibration complete

Save complete

EEPROM fault

Faulty calibration (no save)

For detailed configuration
information, see chapter 5 of your
RTD Input Module User Manual
(publication 1771-6.5.76).

Configure the Module