4-4 Connecting the Network Interface Card

Publication 1784-UM527B-EN-P - October 2003

Before You Begin

Before you make the connections, make sure you have the correct cable.

The 1784-PKTX, -PKTXD card ships with 82

Ω and 150Ω resistors and with the

DH+/remote I/O and DH-485 mating connectors.
For additional cable information, see these Allen-Bradley publications:

WARNING

If you connect or disconnect the communications cable with power
applied to this module or any device on the network, an electrical arc
can occur. This could cause an explosion in hazardous location
installations.

For connections to:

Use this cable:

And these termination
resistors:

Network Cable (build your own)

Remote I/O

1770-CD

!"

Belden #9463

82

Ω or 150Ω

DH+

1770-CD

!"

Belden #9463

150

Ω for 57.6K bits/sec

150

Ω for 115.2K bits/sec

82

Ω for 230.4K bits/sec

DH-485

Belden #3106A

!$

not needed

Point-to-point Cable (prefabricated)

Original PLC-5

1784-CP12

not needed

SLC 5/04 processors

(direct DH+ connection)

Enhanced PLC-5

SLC 5

1756-DHRIO

1784-CP13 (DH+)

not needed

SLC family processors

(direct DH-485 connection)

1784-CP14 (DH-485

not needed

!

Cables used for construction of custom cables

$

Mating Connector: A-B PN 941999-06 or Phoenix Order No. 1849406

"

Mating Connector: A-B PN 941999-03 or Phoenix Order No. 1849396

Publication Title

Publication Number

1784-CP12 Cable Packing Data

1784-2.41

1784-CP13 Cable Packing Data

1784-2.44

1784-CP14 Cable Packing Data

1784-2.45