Rockwell Automation 1784-PKTX_PKTXD Communication Card User Manual User Manual

Page 32

Advertising
background image

A-2 Specifications

Publication 1784-UM527B-EN-P - October 2003

Non-Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50g

Emissions

CISPR 11:

Group 1, Class A

ESD Immunity

IEC 61000-4-2:

4kV contact discharges

8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

EFT/B Immunity

IEC 61000-4-4:

±2kV at 5kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:

±2kV line-earth (CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Enclosure Type Rating

None (open-style)

Power Dissipation (for the PKTXD)

4.0W 800ma @ 5Vdc

Isolation voltage

Tested to 500Vac for 60 sec

Driver development for remote I/O

6001-RIO, contains binary files and example C code for remote I/O
communication

Driver development for DH+ or
DH-485

Use the RSLinx PKTx driver.

1784-DP4, contains binary files and example C code for DH+ or DH-485
communication. (non-Windows)

Agency certification

(when product is marked)

c-UR-us UL Recognized Component Industrial Control Equipment

for Class I, Division 2 Group A,B,C,D Hazardous

Locations, certified for US and Canada

CE

(2)

European Union 89/336/EEC EMC Directive, compliant with:

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

C-Tick

(2)

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

(1)

Refer to publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines for Noise Immunity.

(2)

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other
certification details.

Advertising