Table 4.1 selecting the external resistor, Interpreting the status leds, Table 4.2 dh+ status led – Rockwell Automation 1784-PKTX_PKTXD Communication Card User Manual User Manual

Page 28: Interpreting the status leds -12

Advertising
background image

4-12 Connecting the Network Interface Card

Publication 1784-UM527B-EN-P - October 2003

Table 4.1 Selecting the External Resistor

Interpreting the Status LEDs

What the LEDs mean depends on which protocol is running. Only the PKTXD uses both
LEDs. The left LED (labeled |) is for the top channel on a PKTXD and the other is for the
second, lower channel. A PKTX has only one channel (but multiple connectors depending on
protocol) so only one LED is used.
Table 4.2 explains the DH+ Status LED. Table 4.3 on page 4-13 explains the DH-485 Status
LED. Table 4.4 on page 4-13 explains the Remote I/O Scanner Mode LED.

The maximum number of:

If your remote I/O link:

use this
resistor
rating:

physical
devices
connected on
the link:

racks that you
can scan on the
link:

operates at 230.4 K bits

82

32

16

operates at 57.6 or 115.2K bit/s, and no devices listed
below are linked:

Scanners:

1771-SN; 1772-SD, -SD2;

1775-SR, -S4A, -S4B;

Adapters

1771-AS; 1771-ASB (series A only);
1771-DCM

Miscellaneous

1771-AF

connects to any device listed below:

150

16

16

Scanners

1771-SN; 1772-SD, -SD2;

1775-SR, -S4A, -S4B;

Adapters

1771-AS; 1771-ASB (series A only);
1771-DCM

Miscellaneous

1771-AF

operates at 57.6 or 115.2K bit/s, and you do not require
over 16 physical devices

Table 4.2 DH+ Status LED

LED State

Means

off

channel not online

blinking green

it is the only node on the network

solid green

online and receiving token

blinking red

duplicate node

solid red

failed selftest