Install Your FlexArmor PROFIBUS Adapter Module

To install the PROFIBUS Adapter Module:

1. Hold the adapter at an angle and engage the top of the

adapter in the indention on the rear of the Baseplate.

2. Press the module down flush with the panel until the locking

lever locks.

3. Screw down the module retaining screws to ensure IP67

compliance.

Communicate with Your FlexArmor System

Use PROFIBUS software to configure your FlexArmor system.
Download the GSD file for this adapter from the following website:
www.ab.com/io/networks/gsd.

IMPORTANT

The adapter module must be installed only in the
adapter slot, the second position from the left.

IMPORTANT

Torque the screws to 0.5-0.7 Nm. (4.43 - 6.2 inch
pounds).

IMPORTANT

I/O modules can be installed in any slot location
to the right of the adapter module. The adapter is
capable of addressing up to eight I/O modules.