Troubleshooting with the indicators, Specifications – Rockwell Automation 1798-APB FlexArmor PROFIBUS Adapter Module User Manual

Page 6

Advertising
background image

6 FlexArmor PROFIBUS Adapter Module

Publication 1798-IN011A-EN-P - March 2002

Troubleshooting with the Indicators

Diagnostic indicators are located on the front of the adapter module.
They show both normal operation and error conditions in your
PROFIBUS I/O system. The indicators are:

STATUS

PROFIBUS

The following table describes status indicators.

The following table describes PROFIBUS status indicators.

Specifications

STATUS Indicator

Indicator

Status

OFF

No power

Solid Green

Normal operation

Flashing Red/OFF

Recoverable fault
- FlexArmor I/O module bad
- Incorrect FlexArmor I/O module installed
- Node address changed since power up

Solid Red

Unrecoverable fault

PROFIBUS Indicator

Indicator

Status

OFF

No power or no communication

Solid Green

Data is being transmitted and received

Flashing Red/OFF

Recoverable fault
- Invalid Send Parameter data
- Invalid Check Configuration data

Solid Red

Unrecoverable fault
- Unable to communicate

FlexArmor PROFIBUS Adapter Specifications
Network Protocol

PROFIBUS-DP (EN50170)

Communication of the slave with a Class 1 master

Communication of the slave with a Class 2 master

Redundancy

Not supported

Repeater Control Signal

RS485 signal

Implementation Type

SPC3