Troubleshooting with the Indicators
Diagnostic indicators are located on the front of the adapter module.
They show both normal operation and error conditions in your
PROFIBUS I/O system. The indicators are:
•
STATUS
•
PROFIBUS
The following table describes status indicators.
The following table describes PROFIBUS status indicators.
Specifications
STATUS Indicator
Indicator
Status
OFF
No power
Solid Green
Normal operation
Flashing Red/OFF
Recoverable fault
- FlexArmor I/O module bad
- Incorrect FlexArmor I/O module installed
- Node address changed since power up
Solid Red
Unrecoverable fault
PROFIBUS Indicator
Indicator
Status
OFF
No power or no communication
Solid Green
Data is being transmitted and received
Flashing Red/OFF
Recoverable fault
- Invalid Send Parameter data
- Invalid Check Configuration data
Solid Red
Unrecoverable fault
- Unable to communicate
FlexArmor PROFIBUS Adapter Specifications
Network Protocol
PROFIBUS-DP (EN50170)
•
Communication of the slave with a Class 1 master
•
Communication of the slave with a Class 2 master
Redundancy
Not supported
Repeater Control Signal
RS485 signal
Implementation Type
SPC3