Rockwell Automation 1798-APB FlexArmor PROFIBUS Adapter Module User Manual

Page 7

Advertising
background image

FlexArmor PROFIBUS Adapter Module 7

Publication 1798-IN011A-EN-P - March 2002

FlexArmor PROFIBUS Adapter Specifications (continued)
Freeze Mode

Supported

Sync Mode

Supported

Auto Baud Rate

Supported

Fail Safe Mode

Not Supported

Station Type

Slave

FMS Support

Not supported

Number of nodes

100 maximum - rotary switch type node address setting
(00-99)

Network Length/
Communication rate

9.6KBPS @ 1000m (3280ft)
19.2KBPS @ 1000m (3280ft)
45.45KBPS @ 1000m (3280ft)
93.75KBPS @ 1000m (3280ft)
187.5KBPS @ 1000m (3280ft)
500KBPS @ 400m (1312ft)
3MBPS @ 100m (328ft)
6MBPS @ 100m (328ft)
12MBPS @ 100m (328ft)

External DC Power (Input Power:)
Voltage (24V dc nom.)
Current

10-28.8V dc: 5% AC ripple
400 mA @ 24V dc

FlexBus (Output Power):
Voltage (5V dc nom.)
Current

4.75 - 5.2V dc; 5% AC ripple
640 mA @ 5.2V dc

Indicators

1 red/green module status
1 red/green network status

Wiring

Refer to publication 1770-4.1 Programmable Controller
Wiring and Grounding Guidelines

Isolation

Type test 1250Vac rms for 60 seconds between field
power and PROFIBUS (I/O to logic)

Dimensions (H x D x W)

118 mm X 50 mm X 40 mm
4.63 in. X 1.95 in. X 1.58 in.

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry
Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
–25 to 85°C (–13 to 185°F)

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A