Attach the adapter plates to the panel – Rockwell Automation 2711P-RAK6 Cutout Adapter Kit for PVPlus 600 Keypad or Keypad Touch Terminals User Manual

Page 5

Advertising
background image

Cutout Adapter Kit 5

Publication 2711P-IN021A-MU-P

Attach the Adapter Plates to the Panel

1. The studs on the front adapter plate fit within the existing cutout of the

terminal.

2. Place the front adapter plate into the panel cutout until the sealing gasket

material is firmly against the front of the panel.

3. Mount the rear adapter plate to the front adapter plate studs from the back

of the panel (flat side of rear adapter plate towards front of enclosure).
Using the supplied nuts and lock washers, fasten the rear adapter plate to the studs of
the front adapter plate.

4. Using the torque wrench, tighten the nuts to no more than 1.36 N•m

(12 in-lb) to maintain a NEMA Type 4X rating. Do not overtighten.

Front Adapter Plate

Rear Adapter Plate
Clamp

Front of Panel or Enclosure

Nut and Washer

Inside of Panel or Enclosure

Advertising