Rockwell Automation 61C542 Voltage Input module User Manual
Page 34

4Ć16
4.3
Monitoring Data and
Configuration Register Values
Run the ReSource Programming Executive Software. Use the
MONITORfunction in DCS 5000/ AutoMax systems or the POINT
MONITORfunction in AutoMate systems to check the contents of the
registers. Note that you need to configure the channels before you
can monitor their contents.
Status register values are in hexadecimal format. All other register
values are in decimal.
4.4
Sample DCS 5000/AutoMax
Voltage Input Application Task
The sample DCS 5000/AutoMax voltage input application task in
figure 4.12 is written for a Voltage Input module in slot 2 which is
connected to three singleĆended, 0Ć10V transmitters, which are in
turn wired into a pressure polymerization process.
One transmitter is used to sense the level of the material in the tank.
The second transmitter has its span calibrated for 0 to 3000 psig
(gauge poundsĆperĆsquare inch) and is used during startup
operation. The third transmitter has its span calibrated for 1940 to
1960 psig and is used for process control.
Channel 0: Material Level
Process Parameters
Configuration Values
D Maximum = 20 feet
Reg. 24 = 2000 (Scaled in
0.01 Ft)
D Minimum = - 1 feet
Reg. 25 = -100
D High High Alarm = 18 feet
Reg. 27 = 1800
D High Alarm = 16 feet
Reg. 28 = 1600
D Low Alarm = 4 feet
Reg. 29 = 400
D Low Low Alarm = 0 feet
Reg. 30 = 0
Channel 1: Startup Pressure
Process Parameters
Configuration Values
D Maximum = 3000 psig
Reg. 24 = 3000 (Scaled
directly in psig)
D Minimum = 0 psig
Reg. 25 = 0
D High High Alarm = 2500 psig
Reg. 27 = 2500
D High Alarm = 2000 psig
Reg. 28 = 2000
D Low Alarm = 500 psig
Reg. 29 = 500
D Low Low Alarm = 250 psig
Reg. 30 = 250