Troubleshooting
In this chapter, we describe how to use the adapter’s indicators for
troubleshooting.
Locate the two bi-color indicators on the front panel of the adapter.
They show both normal operation and fault conditions in your Flex
I/O PROFIBUS system. The indicators are:
•
STATUS – this indicator provides device status
•
PROFIBUS – this indicator provides communication link status
Use the following table to determine the indicator conditions and
status.
STATUS Indicator
Indication
Status
OFF
No power
SolidGreen
Normal operation
Flashing Red/OFF
Recoverable fault
- Flex I/O module bad
- Incorrect Flex I/O module installed
- Node address changed since
power up
SolidRed
Unrecoverable fault
PROFIBUS Indicator
Indication
Status
OFF
No power or no communication
SolidGreen
Data is being transmittedandrecieved
Flashing Red/OFF
Recoverable fault
- InvalidSendParameter data
- InvalidCheck Configuration data
SolidRed
Unrecoverable fault
- Unable to communicate
STATUS indicator
(green/red)
PROFIBUS indicator
(green/red)