2–29
How Communication Takes Place and I/O Image Table Mapping
Publication 1794ĆUM057B-EN-P - November 2001
Description
Decimal Bit
(Octal Bit)
Word
Write Word 1
00-01 (00-01) Module Data Type
Bit
01
00
Definition
0
0
o
C (default)
0
1
o
F
1
0
Bipolar counts scaled between -32768 and +32767
1
1
Unipolar counts scaled between 0 and 65535
Bit 02 (02)
Fixed Digital Filter - When this bit is set (1), a software digital filter is enabled. This filter settles to
100% of a Full Scale step input in 60 scans.
03-05 (03-05) A/D Filter First Notch Frequency
Bit
05
04
03
Definition
0
0
0
10Hz (default)
0
0
1
25Hz
0
1
0
50Hz
0
1
1
60Hz
1
0
0
100Hz
1
0
1
250Hz
1
1
0
500Hz
1
1
1
1000hZ
06 (06)
Calibration High/Low bit - This bit is set during gain calibration; reset during offset calibration.
07 (07)
Calibration clock- this bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate
calibration.
08-15 (10-17) Calibration mask- The channel, or channels, to be calibrated will have the correct mask bit set. Bit 8
corresponds to channel 0, bit 9 to channel 1, and so on.