Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module User Manual User Manual
Page 27

2–7
How Communication Takes Place and I/O Image Table Mapping
Publication 1794ĆUM057B-EN-P - November 2001
1794ĆOB8 - 8Ćpoint Discrete Output Module Image Table Mapping
Module Image
Outputs
Input Size
Output Size
0 or 1 Word
1 or 2 Words
I/O Image
Not used
Not used
Read
Write
Not used
1794ĆOB8 Memory Map
DecimalBit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Size
Octal. Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read Words
Not used
Read Word 1
Not used
O7
O6
O5
O4
O3
O2
O1
O0
Write Word 1
Not used
Write Word 2
Where O = Output value (O0 corresponds to output 0, O1 corresponds to output 1, etc.)
1794ĆOB16 - 16Ćpoint Discrete Output Module Image Table
Mapping
Module Image
Outputs
Input Size
Output Size
0 or 1 Word
1 or 2 Words
I/O Image
Not used
Not used
Read
Write
1794ĆOB16 Memory Map
Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Size
Oct. Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read/Write Words
Not used
Read Word 1
O15 O14 O13 O12 O11 O10
O9
O8
O7
O6
O5
O4
O3
O2
O1
O0
Write Word 1
Not used
Write Word 2
Where O = Output value (O0 corresponds to output 0, O1 corresponds to output 1, etc.)