Rockwell Automation 2080-LC50-48AWB_48QBB_48QVB_48QWB Micro850 48-Point Programmable Controllers Installation Instructions User Manual

Page 15

Advertising
background image

Micro850 48 Point Programmable Controllers 15

Publication 2080-IN008B-EN-P - April 2014

Pilot duty rating

C300, R150

Isolation
voltage

250V
(continuous),
Reinforced
Insulation Type,
Output to Aux and
Network, Inputs
to Outputs.
Type tested for
60 s @ 3250V DC
Output to Aux and
Network, Inputs
to Outputs.
150V
(continuous),
Reinforced
Insulation Type,
Input to Aux and
Network
Type tested for
60 s @ 1950V DC
Input to Aux and
Network.

250V
(continuous),
Reinforced
Insulation Type,
Output to Aux and
Network, Inputs
to Outputs.
Type tested for
60 s @ 3250V DC
Output to Aux and
Network, Inputs
to Outputs.
50V (continuous),
Reinforced
Insulation Type,
Input to Aux and
Network
Type tested for
60 s @ 720V DC,
Inputs to Aux and
Network.

50V (continuous), Reinforced
Insulation Type, I/O to Aux and
Network, Inputs to Outputs.
Type tested for 60 s @ 720V DC, I/O
to Aux and Network, Inputs to
Outputs.

North American
temp code

T4

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication

1770-4.1

.

General Specifications

Attribute

2080-LC50

-48AWB

-48QWB

-48QVB

-48QBB