Rockwell Automation 2080-LC50-48AWB_48QBB_48QVB_48QWB Micro850 48-Point Programmable Controllers Installation Instructions User Manual

Page 18

Advertising
background image

18 Micro850 48 Point Programmable Controllers

Publication 2080-IN008B-EN-P - April 2014

Environmental Specifications

Attribute

Value

Temperature,
operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)

Temperature,
surrounding air, max

65 °C (149 °F)

Temperature,
non-operating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g

Shock,
non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
DIN mount: 25 g
PANEL mount: 35 g

Emissions

CISPR 11
Group 1, Class A

ESD immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF
immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on signal ports
±1 kV @ 5 kHz on communication ports

Surge transient
immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±1 kV line-earth(CM) on communication ports

Conducted RF
immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Advertising