Rockwell Automation 2080-LC50-48AWB_48QBB_48QVB_48QWB Micro850 48-Point Programmable Controllers Installation Instructions User Manual

Page 16

Advertising
background image

16 Micro850 48 Point Programmable Controllers

Publication 2080-IN008B-EN-P - April 2014

Input Specifications

Attribute

2080-LC50-48AWB

2080-LC50-48QWB / 2080-LC50-48QVB /
2080-LC50-48QBB

120V AC Input

High Speed
DC Input
(Inputs 0…11)

Standard DC Input
(Inputs 12 and
higher)

Number of inputs

28

12

16

Input group to backplane
isolation

Verified by the
following dielectric
tests: 1950V AC for 2 s
150V working voltage
(IEC Class 2 reinforced
insulation)

Verified by the following dielectric tests:
720V DC for 2 s
50V DC working voltage (IEC Class 2
reinforced insulation)

Voltage category

110V AC

12/24V sink/source (standard)
24V sink/source (high-speed)

Operating voltage range

132V, 60Hz AC max

16.8…26.4V DC
@ 65°C (149°F)
16.8…30.0V DC
@ 30°C (86°F)

10…26.4V DC @
65°C (149°F)
10…30.0V DC @
30°C (86°F)

Off-state voltage, max

20V AC

5V DC

Off-state current, max

1.5 mA

1.5 mA

On-state current, min

5 mA @ 79V AC

5.0 mA @ 16.8V
DC

1.8 mA @ 10V DC

On-state current, nom

12 mA @ 120V AC

7.6 mA @ 24V DC 6.15 mA @ 24V DC

On-state current, max

16 mA @ 132V AC

12.0 mA @ 30V DC

Nominal impedance

12 k

Ω @ 50 Hz

10 k

Ω @ 60 Hz

3 k

Ω

3.74 k

Ω

IEC input compatibility

Type 3

Inrush current, max

250 mA @ 120V AC

Input frequency, max

63 Hz

IMPORTANT

For 24V AC specifications, refer to the Micro830 and Micro850 User Manual,
publication

2080-UM002

.

Advertising