Mount the Kinetix 6000 Shunt Module

Follow these steps to mount your 2094-BSP2 shunt module.

1. Remove the protective boot from the power rail connector.

2. Remove the label (applied to back and side of module) covering the pins

that mate with the power rail.

3. Hang the mounting bracket from the slot on the power rail.

TIP

All modules mount to the power rail by using the same technique, however, the
IAM module is shown in this example.

IMPORTANT

The shunt module must be positioned to the right of the IAM and AM
modules.

ATTENTION

To avoid damage to the pins located on the back of the shunt module
and to make sure that module pins mate properly with the power rail,
hang modules as shown in steps 3…6.

The power rail must be mounted vertically on the panel before hanging
modules on the power rail. Do not mount modules if the power rail is
horizontal.

Slots for additional axis modules,

shunt module, or slot-filler modules.

Power Rail Slot

Mounting Bracket

Power Rail

IAM, AM, Shunt, or

Slot-filler Module

(IAM module is shown)