Ethernet cable, Marine applications – Rockwell Automation 2711P-Rxxxx Logic Module, Internal CompactFlash, and RAM User Manual

Page 11

Advertising
background image

Logic Module, Internal CompactFlash, and RAM 11

Publication 2711P-IN004J-EN-P - September 2009

Ethernet Cable

Use Belden 7921A shielded Ethernet Category 5e cable according to TIA 568-B.1 and RJ45
connector according to IEC 60603-7 for compliance with Marine emissions limits and
European Union 89/336/EEC EMC Directive.

The maximum cable length between the terminal’s Ethernet port and a 10/100 Base-T port
on an Ethernet hub (without repeaters or fiber) is 100 m (328 ft). For additional information,
refer to the EtherNet/IP Media Planning and Installation Manual, publication

ENET-IN001

.

Marine Applications

Isolated DC logic modules require a line filter for use in marine applications. Use Corcom
6VW1 or equivalent filter type.

Earth/ground

GND to ground bus

Earth/ground

GND to ground bus

DC-

DC+

1 m (39 in.) max.

Line

Filter

PanelView Plus

Marine Terminal

DC- DC+

GND