Battery Precautions
Replace the Battery in PanelView Plus Terminals
Follow these steps to replace the battery in the logic module of PanelView Plus or PanelView 
Plus CE terminals.
1. Disconnect power from the terminal.
2. Place the terminal, display side down, on a flat stable surface.
3. Detach the communication module, if attached, from the logic module by removing
the four screws.
4. Loosen the six captive screws that attach the logic module to the display module.
5. Carefully lift the logic module away from the terminal and turn over to expose the
circuit board.
WARNING
When you connect or disconnect the battery, an electrical arc can occur. This could cause 
an explosion in hazardous location installations. Be sure that power is removed or the 
area is nonhazardous before proceeding. 
For safety information on the handling of lithium batteries, including handling and 
disposal of leaking batteries, see Guidelines for Handling Lithium Batteries, publication 
. Replace the battery only with the indicated catalog number.
Do not dispose of battery in a fire or incinerator. Dispose of used batteries in accordance 
with local regulations.
Store batteries in a cool, dry environment. We recommend 25 °C (77 °F) with 40…60% 
relative humidity. You may store batteries for up to 30 days between -45…85 °C 
(-49…185 °F), such as during transportation. To avoid possible leakage, do not store 
batteries above 60 °C (140 °F) for more than 30 days.
Logic Module
Communication Module
Screw
Captive 
Screw
Display Module