18Ć32

AutoMax Programming Executive Version 3.x

Other Methods of Setting UP Meter Ports
PMI meter ports can be set up during DPS parameter entry on on the

Monitor Setup UDC/PMI menu. UDC meter ports can be set up via

registers 1001-1017 in a UDC application task or on the Monitor

Setup UDC/PMI menu. The setup information may be retained after a

Stop All or power cycle depending on the method used. See the

table below.

Table 18.1 - Meter Port Setup Retention

UDC Setup

via Monitor

Menu

UDC Setup via

Application

Task (Reg.

1001Ć 1017)

PMI Setup

during

Parameter

Entry

PMI Setup

via Monitor

Menu

Retained after

Stop All?

Yes

Yes*

Yes

No**

Retained after

power cycle

No

Yes*

Yes

No**

ă*Original task setup is retained.
**If the PMI meter ports are set up using the parameter screens and then later set

up again using the Monitor menu, the setup in the parameter screens will still

be retained.

ON LINE direct Udc Slot 06 AUTOMAX

C: \AMXLIB3\SYSDNYR\RACK1

Monitor Setup UDC/PMI

EscăExit

UDC

AăPMI

BăPMI

F1 Help

Loc Port Task

VarName/RegNum

UDC ă1 S5ASPD CML_WCO%

UDC ă2 S5ASPD RES_GAN

UDC ă3

00201

UDC ă4 00690
Loc

Port Par Num

Description

Val @Ć10V Val @+10V

PMIĆA

1

ă4

ArmVolt.(Volts E0)

-32767

32700

PMIĆA

2

16

ACRMSLineV(Volts E0)

0

10

PMIĆA

3

ă3

ArmCurFdBk(Amps E1)

0

32700

PMIĆA

4

PMIĆB

1

PMIĆB

2

PMIĆB

3

PMIĆB

4

Bit

Val @Ć10V

Val@+10V

0

32767

0

255

3

-100

100

Figure 18.9 Ć UDC Setup Screen

You can display and output to the selected port any variable mapped

to a UDC register (common) or any local variable. The task name is

required for local variables.