S.3 loss of task modifications made onćline, S.4 tasks in the rack do not go into run – Rockwell Automation 57C620 AutoMax Programming Executive Version 3.8 User Manual

Page 293

Advertising
background image

SĆ3

What Can Go Wrong When Loading Tasks and Files

and the Programming Executive software will automatically load the

files in the correct sequence.

S.2

Processor or Universal Drive Controller

Module LEDs Displaying Errors

If the Processor module OK LED is off or the two sevenĆsegment

LEDs on the Processor faceplate display a code, see instruction

manual JĆ3650, which describes the AutoMax Processor module. If

the sevenĆsegment LEDs display LO" (reading top to bottom), this

simply means that you need to load the operating system to the

Processor.
For racks containing a Universal Drive Controller module, the OS

OK" LED on the module will turn on only after it has received its

operating system. See instruction manual SĆ3007 for more

information about the Universal Drive Controller module.

S.3

Loss of Task Modifications Made OnĆLine

If you or someone else makes changes to tunable variables in

existing application tasks in the rack, or makes changes to Ladder

Logic/PC tasks on the rack, you must save those tasks back from

the rack to the personal computer. This will ensure that you have a

copy of the same task on both the personal computer and the rack.
If you do not save tasks back from the rack to the personal

computer, and a situation arises that requires you to reĆload all tasks

to the rack, the version of each task that does exist on the personal

computer will write over the version in the rack when all tasks are

loaded. If the version of the task on the personal computer is not the

most upĆtoĆdate version, that is, you or someone else made the

changes described above to tasks in the rack, the changes will be

lost.

S.4

Tasks in the Rack Do Not Go into Run

Tasks in the rack will go into run, i.e., execute the instructions stored

in the task, when they are put into run by the operator using the

RUN command. The status (run, stop, or error) of all tasks in the

rack can be accessed from the ON LINE menu display. If tasks are

not running and there is no error in the rack, you can use the RUN

command to start a task or all tasks in the rack.
The nature of the application may require that tasks go back into run

after a power cycle (power going off, then on). This is made possible

by using the AUTOĆRUN software switch. If AUTOĆRUN is enabled

when power is turned off and then turned on again, all tasks that

were in run when power went off will go into run again, assuming

there are no errors in the rack.
If AUTOĆRUN is enabled and tasks do not automatically go into run

when power is turned back on, there is an error in the rack.

Advertising