FlexArmor Analog Input Module 5

Publication 1798-IN007A-EN-P - April 2002

4. Screw down the module retaining screws to ensure IP67

compliance.

Connect the Cordset to the FlexArmor Module

The module uses 5 pin micro (12mm) style PCB mounted connectors.

Four micro caps cover the I/O connectors on the module. Remove
the caps and connect your cables to the appropriate ports. Keep the
caps in place on any unused connector to maintain the IP67 rating.

A pinout diagram for the connectors is shown below.

IMPORTANT

•

Torque the screws to 0.5-0.7 Nm. (4.43 - 6.2
inch pounds).

•

Dust caps must have 4 inch pounds of torque
to maintain IP67 compliance.

ATTENTION

!

•

Make sure all connectors and caps are
securely tightened to properly seal the
connections against leaks and maintain IP67
requirements.

•

For maximum noise immunity, input and
output cable return wires must be properly
terminated. When inputs and outputs are
connected in loopback, return wires should
be connected together.

•

I/O cable length should be less than 30
meters.

42652

Female Input Micro-Connector

(View into Socket)

Pin 1 Sensor Power
Pin 2 Current Input
Pin 3 Sensor Common
Pin 4 Voltage Input
Pin 5 Not Used