Troubleshooting with the indicators, Specifications – Rockwell Automation 1798-IE4 FlexArmor Analog Input Module User Manual

Page 6

Advertising
background image

6 FlexArmor Analog Input Module

Publication 1798-IN007A-EN-P - April 2002

Troubleshooting with the Indicators

The following table describes the status indicator on the analog input

modules.

Specifications

I/O Status Indicators

Function

Indicator

Status

Fault LED Red

Off

Sensor Power Short
Normal

Specifications - 1798-IE4 Analog Input Module

Module Type

Analog Input

Number of Channels

4 single-ended, non-isolated

ResolutionBits
Voltage/Cnt
Current/Cnt

12 - Unipolar, 11+ sign - Bipolar
2.56 mV - Unipolar; 5.13 mV - Bipolar
5.13 uA

Data Format

16 bit; 2’s complement; left-justified

Conversion Type

Successive approximation

Conversion Rate

256 us - All channels

Current Terminal

4-20 mA; 0-20 mA (user configurable)

Voltage Terminal

±10V; 0-10V (user configurable)

Normal Mode Rejection
Voltage Terminal

Current Terminal

-3 db @ 17 Hz; -20 db/decade;
-10 db @ 50 Hz; 11.4 db @ 60 Hz
-3 db @ 9 Hz; -20 db/decade;
-15.3 db @ 50 Hz; -16.8 db @ 60 Hz

Step Response to 63%
Voltage Terminal
Current Terminal

9.4 ms
18.2 ms

Impedance: Voltage Terminal

Current Terminal

100 k

; 200 k

@ DC

238

Absolute Accuracy
Voltage Terminal
Current Terminal

0.20% FS @ 25°C
0.20% FS @ 25°C

Accuracy Drift: Voltage Terminal

Current Terminal

0.00428% FS per°C
0.00407% FS per°C

Calibration

None Required

Maximum Overload
Voltage Terminal
Current Terminal

Single channel; continuous
30V
32 mA

Isolation Voltage

850V dc channel-to-system for 1s

FlexBus Current

10 mA maximum

Sensor Source Current
(per connector)

50 mA

Power dissipation

2.5W @ 28.8V dc