Rockwell Automation 2706 Dataliner 20 Message Display User Manual
Page 12
Dataliner DL20 Message Display
12
•
Output leads from the power-line filter to the Dataliner must be 10 cm (4 in.) or
less.
•
Both Dataliner and power-line filter must be connected to a low impedance earth
ground
•
All parts of the grounding system must be connected together with low
impedance connections. Keep all ground connections as short as possible
•
Power-line filter must be connected to earth ground before connecting the power
source.
•
Do not run signal wiring and power wiring in the same conduit.
•
When control or communication wires must cross, they should cross at an angle
as close to 90 degrees as possible.
•
Follow Dataliner display shielded cable requirements as specified in the user
manual.
•
Make sure cable shielding connections and terminations are connected as
specified in the appropriate Dataliner User Manual.
•
Keep the filter line side leads well separated from the load side leads.