Installing display in panel, Mounting the dl20 – Rockwell Automation 2706 Dataliner 20 Message Display User Manual

Page 5

Advertising
background image

Dataliner DL20 Message Display

5

Installing Display in Panel

To install the Dataliner display:

!

ATTENTION:

Disconnect all electrical power from the panel before

making cutout.

Make sure the area around the panel cutout is clear.

Take precautions so that metal cuttings do not enter any components
that may already be installed in panel.

Failure to follow this warning may result in personal injury or damage
to the panel components.

Mounting the DL20

The following figures provide panel cutout dimensions and overall dimensions for
the DL20.

You can mount the DL20 in a custom panel or enclosure. Dataliner enclosures
Catalog Numbers 2706-NE1 (one- or two-line display) and 2706-NE2 (four-line
display) are available When the DL20 is properly installed, the faceplate of the
DL20 provides a NEMA Type 12/13 enclosure integrity.

To install the DL20, perform the following steps:

1.

Cut and drill the appropriate mounting holes in the enclosure or panel.

2.

Remove the six mounting nuts from the hardware kit included with the DL20.

3.

Position the DL20 in the panel or enclosure mounting hole.

4.

Install and tighten the six nuts on the mounting studs to a torque of 14 in

lbs

(1.6N

m) each.

!

ATTENTION:

Mounting nuts must be tightened to a torque of 14

inch-pounds to provide a proper seal and to prevent potential damage to
the display. Allen-Bradley assumes no responsibility for water or
chemical damage to the display or other equipment within the enclosure
because of improper installation.

Advertising