Publication 2080-IN009B-EN-P - April 2014

Grounding Your Analog Cable

Use shielded communication cable (Belden #8761). The Belden cable has two signal wires (black
and clear), one drain wire, and a foil shield. The drain wire and foil shield must be grounded at
one end of the cable.

Wiring Your Plug-In Modules

Wiring diagrams for your Micro800 plug-in modules are available in the Rockwell Automation
Literature Library,

http://rockwellautomation.com/literature

.

Wire the Controller

Serial Port Terminal Block

IMPORTANT

Do not ground the drain wire and foil shield at both ends of the cable.

Foil Shield

Black Wire

Drain Wire

Clear Wire

44531

Insulation

D-

D+

G

Rx

Tx

1

2

3

4

5

6

G

46213

(View into terminal block)
Pin 1 RS485 Data +
Pin 2 RS485 Data -

Pin3 RS485 Ground

(1)

Pin 4 RS232 Receive
Pin 5 RS232 Transmit

Pin 6 RS232 Ground

(1)

(1)

Non-isolated.