Publication 2080-IN009B-EN-P - April 2014

PWM Output Duty Cycle Error

Turn On/Off time for the Micro820 controllers for the PWM output port is 0.2

µs and 2.5 µs

max, respectively. Duty cycle error is:
Positive error = 2.5

µs * F

Negative error = -0.2

µs * F

The plot below shows duty cycle error vs. frequency.

To get the duty cycle error at a certain frequency, for example, the user sets frequency to 20 KHz,
and sets duty cycle to 30% in Connected Components Workbench, then actual duty cycle is

.

Controller current, max total

3 A

Turn-on time, max

0.1 ms

0.2

μs

Turn-off time, max

1.0 ms

2.5

μs

Response time, max

10 ms

Frequency rate

NA

2%

(1)

High speed output operation is greater than 5 Khz.

DC Output Specifications for 2080-LC20-20QBB(R)

Attribute

Standard Outputs
(Outputs O-00…O-05)

High Speed Output

(1)

(Output O-06)

30%

+5%

-0.4%.

Er

ro

r (P

er

ce

nt

ag

e)

0.25

0.2

0.15

0.1

0.05

0.0

-0.05

1000

10000

100000

Positive Error

Negative Error