10 FLEX Ex Power Supply

Publication

1797-5.8 - June 2010

Customer Connections

Typical Wiring Configurations

Vin1

Vin2

Chassis GND

IS Isolation

Hazardous to IS

-V
+V

Out 1

-V
+V

Out 2

-V
+V

Out 3

41315

Dual Input

Diodes

IS Limiters

Voltage and Current

-V
+V

Out 4

+

-

+
-

dc

Type of Power Input

IS Power Output

Daisy-chaining

+V, -V

You can use the daisy chain configuration if the
total module power draw is < 8.5 W. Otherwise,
power is connected to individual modules.

Combination

Wiring when total module current
power is greater than 8.5 W.

<8.5 W

+V, -V

Other variations are possible depending
upon individual module power.

<8.5 W

+V, -V

1797-PS2E2

Hazardous

Incoming

Power

IS-safe

Output Power

Keep Wires Separate

41316