Installation in zone 1, 22 – Rockwell Automation 1797-PS2E2 FLEX Ex Power Supply User Manual
Page 6
 
6 FLEX Ex Power Supply
Publication
1797-5.8 - June 2010
Make certain that you only connect intrinsically-safe power supplies to other 
intrinsically-safe system modules or adapters to maintain the integrity of the 
intrinsically-safe backplane.
Installation in Zone 1, 22
The 1797-PS2E2 power supply has a protection factor of IP65. Refer to the 
specifications table for the IS module type.
Application
When installing, commissioning, operating, and maintaining devices or device 
components of the FLEX Ex system as intrinsically-safe electrical apparatus 
in potentially explosive atmospheres according to EN 60079-11, you must 
heed the EC- type examination certificate and the applicable national and 
local construction, installation, and operating regulations.
Zone 1
The power supply can be located in Zone 1. The permissible ambient 
temperature of -20…70 °C must not be exceeded.
Zone 22
The housing type of the power supply is applicable for use in Zone 22. It 
corresponds with the category 3D acc. to directive 94/9 EC and is marked 
with a type label accordingly. 
WARNING
The power supply cannot be used in an intrinsically safe environment 
after its outputs have been exposed to nonintrinsically safe signals.
41307