Rockwell Automation 1797-PS2E2 FLEX Ex Power Supply User Manual

Page 9

Advertising
background image

FLEX Ex Power Supply 9

Publication

1797-5.8 - June 2010

3. Connect the blue IS-safe output power wiring to the output terminals

making sure all connections are tight.

These power supply outputs provide the input power to the FLEX Ex
modules.

4. Thread the hazardous incoming-power wiring through the black

compression seals.

5. Connect the hazardous incoming-power wiring to the input terminals

making sure all connections are tight.

You can daisy-chain the hazardous incoming-power wiring to further
supplies to simplify system wiring.

6. Replace the lid of the Ex e terminal box.

7. Screw the lid back into place making sure all of the screws are tight.

ATTENTION

Keep hazardous and IS-safe wiring separated in a suitable
fashion. Do not leave long, excess wiring that could bridge
between the hazardous and safe area

s.

Advertising