0 diagnostics and troubleshooting, 1 incorrect data – Rockwell Automation 57C400-1 115V AC/DC Input Module User Manual

Page 19

Advertising
background image

5Ć1

5.0 DIAGNOSTICS AND

TROUBLESHOOTING

This section explains how to troubleshoot the module and field

connections.

5.1

Incorrect Data

Problem: The data is either always off, always on, or different than

expected. The possible causes of this are a module in the wrong slot,

a programming error, or a malfunctioning module. It is also possible

that the input is either not wired or wired to the wrong device. Use the

following procedure to isolate the problem:
Step 1.

Verify that the input module is in the correct slot and that

the I/O definitions are correct.
Refer to figure 3.2. Verify that the slot number being

referenced agrees with the slot number defined in the

configuration. For this module, the register number is

always zero. Verify that the bit number refers to the proper

bit. Note that the bit number and the wire number are not

the same.
For remote I/O installations, also verify that the master slot

and remote drop number are defined correctly.

Step 2.

Verify that the input is wired to the correct device.
Confirm that all connections at the terminal strip are tight.

Connect a voltmeter to the proper points on the terminal

strip and toggle the device. The voltmeter should alternate

between 0 and 115 volts. If this does not happen, there is

a problem with either the external device, the DĆC power

supply, or the wiring to the terminal strip.
Check the cable for continuity between the faceplate

connector and the terminal strip.

Step 3.

Verify that the module can be accessed.
Connect the programming terminal to the system and run

the ReSource Software. Use the I/O MONITOR function.

Toggle the input device to determine whether the bit is

changing state.
If the programmer is able to read the input, the problem is

in the application software (proceed to step 4). If the

programmer cannot read the inputs, the problem is in the

hardware (proceed to step 5).

Step 4.

Verify that the user application program is correct.
Verify that the application program that references the

symbolic names associated with the module has declared

those name COMMON in application tasks.
Verify that the symbolic name in question is being

referenced in the application program. This can be done

indirectly by monitoring the name with the VARIABLE

MONITOR function in the ReSource Software.

Advertising