Rockwell Automation 57C400-1 115V AC/DC Input Module User Manual

Page 20

Advertising
background image

5Ć2

If operation is intermittent, verify that the program reading

the module is executing fast enough to catch all of the

input changes.

Step 5.

Verify that the hardware is working correctly.
Toggle the input device. Verify that the LED associated

with the particular bit is also toggling. If it is not, the input

circuit on the module is malfunctioning.
Verify the hardware functionality by systematically

swapping out modules. After each swap, if the problem is

not corrected, replace the original item before swapping

out the next item.
D To test local I/O, first replace the input module. Next,

replace the processor module(s). If the problem

persists, take all of the modules out of the backplane

except one processor module and the input module. If

the problem is now corrected, one of the other

modules in the rack is malfunctioning. Reconnect the

other modules one at a time until the problem

reappears. If none of these tests reveals the problem,

replace the backplane.

D To test remote I/O, first verify that the remote I/O

system is communicating with the drop that contains

the input module being tested. Next, determine

whether the input module is the only module that is not

working. If more than one module is not working

correctly, the problem most likely lies inthe remote I/O

system. If the problem does not lie in the system, it

probably involves the remote rack.

D To test the remote rack, first replace the input module.

Next, replace the slave remote I/O module. If the

problem persists, take all of the modules out of the

remote backplane except the slave remote I/O module

and the input module. If the problem is now corrected,

one of the other modules in the rack is malfunctioning.

Reconnect the other modules one at a time until the

problem reappears. If the problem proves to be neither

inthe remote I/O system nor inthe remote rack, try

replacing the backplane.

Advertising