2 bus error – Rockwell Automation 57C400-1 115V AC/DC Input Module User Manual

Page 21

Advertising
background image

5Ć3

5.2

Bus Error

Problem: A 31" or 51" through 58" appears on the processor

module's LED. This error message indicates that there was a bus

error when the system attempted to access the module. The possible

causes of this error are a missing module, a module in the wrong

slot, or a malfunctioning module. It is also possible that the user is

attempting to write to registers on the module. Refer to the DCS5000

Processor Module Instruction Manual (JĆ3635) or AutoMax Processor

Module Instruction Manual (JĆ3650) for more information. Use the

following procedure to isolate a bus error:
Step 1.

Verify that the input module is in the correct slot and that

the I/O definitions are correct.
Refer to figure 3.2. Verify that the slot number being

referenced agrees with the slot number defined in the

configuration task. Verify that the register number and bit

number are correct.
For remote I/O installations, also verify that the master slot

and remote drop number are defined correctly.

Step 2.

Verify that the module can be accessed.
Connect the programming terminal to the system and run

the ReSource Software. Use the I/O MONITOR function to

display register 0. If the programmer is able to monitor the

inputs, the problem lies in the application software

(proceed to step 3). If the programmer cannot monitor the

inputs, the problem lies in the hardware (proceed to step

4).

Step 3.

Verify that the user application program is correct.
This module cannot be written to. If a BASIC task caused

the bus error, the error log will contain the statement

number in the task where the error occurred. If a ladder

logic or control block task caused the error, you will need

to search the task for any instances where you used an

input as a ladder logic coil or wrote to it in a control block

task.

Step 4.

Verify that the hardware is working correctly.
Verify the hardware functionality by systematically

swapping out the input module, processor module(s), and

backplane. After each swap, if the problem is not

corrected, replace the original item before swapping out

the next item.
For remote I/O installations, systematically swap out the

input module, the slave remote module, and the

backplane. After each swap, if the problem is not

corrected, replace the original item before swapping out

the next item.

Advertising