6 200 Watt Passive Shunt Module
Connecting to the Shunt Terminal Block
1. Locate the external shunt terminal block (TB2) on your drive.
Figure 3
TB2 Terminal Block and Shunt Connection Schematic
2. Remove the factory installed internal shunt jumper between
terminals 1 and 2 of TB2.
3. Connect the lead wires to terminals 1 and 3 of TB2. Tighten screws
to 1.25 Nm (11 in.-lbs).
4. Gently pull on each wire to make sure it does not release from its
terminal.
5. Re-insert and tighten any loose wires.
6. Connect the lead wires to the terminal block on the bottom of the
external shunt. Polarity is not important. Tighten screws to 2.25
Nm (20 lb-in.).
Connecting to the Ground Terminal
1. Locate the ground terminal stud for the shunt module. Refer to
Figure 4 on page 8 location.
2. Connect a system level ground wire to the ground terminal.
Tighten the terminal nut to 2.25 Nm (20 lb-in.).
3. Connect the other end of the ground wire to the system ground
bus.
IMPORTANT
Ensure that power is not applied to the drive.
TB2
3
2
1
Shunt
Module
Drive
4.5A 600V
slow blow
25 Ohm