Firmware Upgrade Utility

3

To Upgrade DL40 Plus
Firmware

To upgrade the firmware in a DL40 Plus message display:

1. Obtain upgrade firmware files from Allen-Bradley representative or

download from web site.

2. Place the firmware files in the same directory as the upgrade utility.

3. Turn off the power to the DL40 Plus display.

4. Connect the serial port of your computer to the DL40 Plus RS-232 port.

Use the download cable (Catalog No. 2706-NC13) or equivalent. Refer
to the display’s user manual if additional wiring information is required.

5. Apply power to the DL40 Plus after the connections have been made.

6. Make sure your computer is running in a DOS environment C:\ If you

are running Windows 95, select shutdown and restart the computer in
MS-DOS mode.

7. Locate the directory where the UPDATE.EXE file is located and run the

utility. The program sign-on screen is displayed.

8. Press any key to display the main menu.

!

ATTENTION: Downloading firmware erases any existing
application in the DL40 Plus memory. Upload and save the
DL40 Plus application prior to downloading firmware.

Dataliner DL40 Plus

Firmware Update Utility

2706-NR5

Version 1.00 (0D67)

November 30, 1998

Copyright 1998 Allen-Bradley Company, Inc

All rights reserved

Press any key to continue

Update Firmware

Exit to DOS

DL40 Plus Firmware Update Utility v1.00 Allen-Bradley Company (C) 1998