6 Micro800 4-channel Thermocouple/RTD Input Module

Publication 2085-IN007A-EN-P - September 2012

Mount the Module

For more information on proper grounding guidelines, see the Industrial Automation Wiring
and Grounding Guidelines, publication

1770-4.1

.

Module Spacing

Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown.

Module Description

Description

Description

1

Mounting screw hole / mounting foot

5

Module interconnect latch

2

Removable Terminal Block (RTB)

6

DIN rail mounting latch

3

Thermistor

7

I/O status LED

4

RTB hold down screws

This equipment is sensitive to electrostatic discharge (ESD).
Follow ESD prevention guidelines when handling this equipment.

ATTENTION: To comply with UL restrictions, this equipment must be powered from a source
compliant with the following:

Class 2 or Limited Voltage/Current.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connected I/O must be
powered from a source compliant with the following:

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).