Wire the Outputs

Included with your module are two 12-pin Removable Terminal Blocks (RTB). Basic wiring of
the module is shown below.

Basic Wiring to the 2085-IRT4 Module

Specifications

TIP

The module currently ships with the CJC assembly fixed to the module.

General Specifications

Attribute

Value

Number of I/O

4

Dimensions
HxWxD

44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)

Shipping weight, approx.

220 g (7.76 oz)

Bus current draw, max

5V DC, 160 mA
24V DC, 50 mA

Wire size

0.25... 2.5 mm

2

(22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F ), or

greater, 1.2 mm (3/64 in.) insulation max

Wiring category

(1)

2 – on signal ports

Terminal screw torque

0.5…0.6 Nm
(4.4…5.3 lb-in.)

(2)

CH0+

CH0H

CH0L

CH0-

CH1+

CH1H

CH1L

CH1-

NC

NC

NC

NC

CH2+

1

2

1

2a

1a

2

CH2H

CH2L

CH2-

CH3+

CH3H

CH3L

CH3-

CJC+

CJC+

TH

CJC-

TH

CJC-

NC

Shielded cable

Shielded cable

1

2

1

2

1a

Shielded cable

2-wire RTD

4-wire RTD

3-wire RTD

Thermocouple

Shielded cable

mV

OR

45326

If a thermocouple is used, the use of the
supplied CJC assembly is compulsory.

Terminal Block 1