Using the mode function – Rockwell Automation 2707-M232P3_M485P3 DTAM Micro Operator Interface Module User Manual
Page 114

Special Controller Functions
Appendix C
DTAM Micro
C–18
Use the Mode function to change the controller operating mode (Run or
Program) from the DTAM Micro. The mode function displays for an SLC
and PLC-5 controller are different. Both are shown below:
SLC Controllers
1. Select item 2 from the Special Menu to access the Mode function.
You are prompted for an operating mode:
SLC Mode
1=Run
0=Program
2. Press [1] to place the controller in Run mode or [0] to enter the Program
mode.
You are returned to the Main Menu.
PLC-5 Controllers
1. Select item 2 from the Special Menu to access the Mode function.
The PLC-5 must be in Remote Program mode or you will be prompted:
Not in Remote mode
Press ENTER to cont.
2. Depending upon the current mode, you are prompted to change the
controller mode:
If the controller is in Run mode:
If the controller is in Program mode;
PLC is in Run Mode
1=Prog 0=Abort
PLC is in PROG Mode
1=RUN 0=Abort
3. Press [1] or [0] to enter your selection.
You are returned to the Main Menu.
Using the Mode Function