ControlNet Modular Repeater Medium Distance Fiber Module 13

Publication 9904-IN011A-EN-P - October 2000

Status Indicators

The figure below identifies the LEDs on the module.

Figure 6 Status Indicators:

IMPORTANT

Be certain that the fiber cable you connect to Channel 1 (RX)
on one 9904-RPFM repeater to Channel 1 (TX) on the other
9904-RPFM repeater. You can use Channel 1 or Channel 2 on
either module.

IMPORTANT

The total number of fiber repeaters (9904-RPFS, RPFM)
between any two nodes (path) is limited to 5 repeaters and 6
segments. You may have many repeaters in a system, but a
maximum of five repeaters between any two nodes.

Status Indicator (LEDs):

Probable Cause:

Off

Repeater not connected to power supply

Green

Repeater is running without errors. The received data frames
are within specification for bit width distortion.

Flashing Green/Off

No data activity on network.

Channel 2 LED